P2902.1 General.
P2902.2 Plumbing fixtures.
P2902.3 Backflow protection.
P2902.4 Protection of potable water outlets.
P2902.5 Protection of potable water connections.
P2902.6 Location of backflow preventers.
P2902.1 General.
P2902.2 Plumbing fixtures.
P2902.3 Backflow protection.
P2902.4 Protection of potable water outlets.
P2902.5 Protection of potable water connections.
P2902.6 Location of backflow preventers.
P2902.2 Plumbing fixtures.
P2902.3 Backflow protection.
P2902.4 Protection of potable water outlets.
P2902.5 Protection of potable water connections.
P2902.6 Location of backflow preventers.
P2902.1 General.
P2902.2 Plumbing fixtures.
P2902.3 Backflow protection.
P2902.4 Protection of potable water outlets.
P2902.5 Protection of potable water connections.
P2902.6 Location of backflow preventers.
SECTION P2902 PROTECTION OF POTABLE WATER SUPPLY
P2902.1 General. A potable water supply system shall be designed and installed as to prevent contamination from nonpotable liquids, solids or gases being introduced into the potable water supply. Connections shall not be made to a potable water supply in a manner that could contaminate the water supply or provide a cross-connection between the supply and a source of contamination unless an approved backflow-prevention device is provided. Cross-connections between an individual water supply and a potable public water supply shall be prohibited.
P2902.2 Plumbing fixtures. The supply lines and fittings for every plumbing fixture shall be installed to prevent backflow. Plumbing fixture fittings shall provide backflow protection in accordance with ASME A112.18.1.
P2902.3 Backflow protection. A means of protection against backflow shall be provided in accordance with Sections P2902.3.1 through P2902.3.6. Backflow prevention applications shall conform to Table P2902.3, except as specifically stated in Sections P2902.4 through P2902.5.5.
TABLE P2902.3 APPLICATION FOR BACKFLOW PREVENTERS
TABLE P2902.3.1 MINIMUM AIR GAPS
P2902.4 Protection of potable water outlets. Potable water openings and outlets shall be protected by an air gap, reduced pressure principle backflow preventer with atmospheric vent, atmospheric-type vacuum breaker, pressure-type vacuum breaker or hose connection backflow preventer.
Exceptions:P2902.5 Protection of potable water connections. Connections to the potable water shall conform to Sections P2902.5.1 through P2902.5.5.
Exception: Where systems are installed as a portion of the water distribution system in accordance with the requirements of this code and are not provided with a fire department connection, isolation of the water supply system shall not be required.
Exception: Where all solar system piping is a part of the potable water distribution system, in accordance with the requirements of the International Plumbing Code, and all components of the piping system are listed for potable water use, cross-connection protection measures shall not be required.P2902.6 Location of backflow preventers. Access shall be provided to backflow preventers as specified by the manufacturer's installation instructions.
TABLE P2902.3 APPLICATION FOR BACKFLOW PREVENTERS
| | | | STANDARDS |
| Air gap | | Backsiphonage or backpressure | ASME A112.1.2 |
| Air gap fittings for use with plumbing fixtures, appliances and appurtenances | | Backsiphonage or backpressure | ASME A112.1.3 |
| Antisiphon-type fill valves for gravity water closet flush tanks | | Backsiphonage only | ASSE 1002, CSA B125.3 |
| Backflow preventer with intermediate atmospheric vents | | Backpressure or backsiphonage Sizes 1/4″-3/4″ | ASSE 1012, CSA B64.3 |
| Double check backflow prevention assembly and double check fire protection backflow prevention assembly | | Backpressure or backsiphonage Sizes 3/8″- 16″ | ASSE 1015, AWWA C510, CSA B64.5, CSA B64.5.1 |
| Double check detector fire protection backflow prevention assemblies | | Backpressure or backsiphonage (Fire sprinkler systems) Sizes 2″- 16″ | ASSE 1048 |
| Dual-check-valve-type backflow preventer | | Backpressure or backsiphonage Sizes 1/4″- 1″ | ASSE 1024, CSA B64.6 |
| Hose connection backflow preventer | | Low head backpressure, rated working pressure backpressure or backsiphonage Sizes 1/2″- 1″ | ASSE 1052, CSA B64.2.1.1 |
| Hose-connection vacuum breaker | | Low head backpressure or backsiphonage Sizes 1/2″,3/4″, 1″ | ASSE 1011, CSA B64.2, CSA B64.2.1 |
| Laboratory faucet backflow preventer | | Low head backpressure and backsiphonage | ASSE 1035, CSA B64.7 |
| Pipe-applied atmospheric-type vacuum breaker | | Backsiphonage only Sizes 1/4″- 4″ | ASSE 1001, CSA B64.1.1 |
| Pressure vacuum breaker assembly | | Backsiphonage only Sizes 1/2″- 2″ | ASSE 1020, CSA B64.1.2 |
| Reduced pressure detector fire protection backflow prevention assemblies | | Backsiphonage or backpressure (Fire sprinkler systems) | ASSE 1047 |
| Reduced pressure principle backflow preventer and reduced pressure principle fire protection backflow preventer | | Backpressure or backsiphonage Sizes 3/8″- 16″ | ASSE` 1013, AWWA C511, CSA B64.4, CSA B64.4.1 |
| Spillproof vacuum breaker | | Backsiphonage only Sizes 1/4″- 2″ | ASSE 1056 |
| Vacuum breaker wall hydrants, frost-resistant, automatic draining type | | Low head backpressure or backsiphonage Sizes 3/4″- 1″ | ASSE 1019, CSA B64.2.2 |
| For SI: 1 inch = 25.4 mm.
a. Low hazard-See Pollution (Section R202). High hazard-See Contamination (Section R202). b. See Backpressure (Section R202). See Backpressure, Low Head (Section R202). See Backsiphonage (Section R202). |
P2902.3.1 Air gaps.
TABLE P2902.3.1 MINIMUM AIR GAPS
| | | |
| (inches) | (inches) | |
| Effective openings greater than 1 inch | | |
| Lavatories and other fixtures with effective opening not greater than 1/2 inch in diameter | | |
| Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch in diameter | | |
| Sink, laundry trays, gooseneck back faucets and other fixtures with effective openings not greater than 3/4 inch in diameter | | |
| For SI: 1 inch = 25.4 mm. |
| a. Applicable where walls or obstructions are spaced from the nearest inside edge of the spout opening a distance greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls. |
P2902.3.2 Atmospheric-type vacuum breakers.
P2902.3.3 Backflow preventer with intermediate atmospheric vent.
P2902.3.4 Pressure-type vacuum breakers.
P2902.3.5 Reduced pressure principle backflow preventers.
P2902.3.6 Double check-valve assemblies.
P2902.4.1 Fill valves.
P2902.4.2 Deck-mounted and integral vacuum breakers.
P2902.4.3 Hose connection.
Exceptions:
1. This section shall not apply to water heater and boiler drain valves that are provided with hose connection threads and that are intended only for tank or vessel draining.
2. This section shall not apply to water supply valves intended for connection of clothes washing machines where backflow prevention is otherwise provided or is integral with the machine.
P2902.5.1 Connections to boilers.
P2902.5.2 Heat exchangers.
P2902.5.3 Lawn irrigation systems.
P2902.5.4 Connections to automatic fire sprinkler systems.
Exception: Where systems are installed as a portion of the water distribution system in accordance with the requirements of this code and are not provided with a fire department connection, isolation of the water supply system shall not be required.
P2902.5.4.1 Additives or nonpotable source.
P2902.5.5 Solar systems.
Exception: Where all solar system piping is a part of the potable water distribution system, in accordance with the requirements of the International Plumbing Code, and all components of the piping system are listed for potable water use, cross-connection protection measures shall not be required.
P2902.6.1 Outdoor enclosures for backflow prevention devices.
P2902.6.2 Protection of backflow preventers.
P2902.6.3 Relief port piping.

