- State
- [ 2010 California Building Code‚ Title 24‚ Part 2 (First Printing)‚ Includes Errata/Supplement through July 1‚ 2012 ]
- Chapter 12 - Interior Environment
- SECTION 1201 GENERAL
- SECTION 1202 DEFINITIONS
- SECTION 1203 VENTILATION
- SECTION 1204 TEMPERATURE CONTROL
- SECTION 1205 LIGHTING
- SECTION 1206 YARDS OR COURTS
- SECTION 1207 [HCD 1& HCD 2] SOUND TRANSMISSION
- SECTION 1208 INTERIOR SPACE DIMENSIONS
- SECTION 1209 ACCESS TO UNOCCUPIED SPACES
- SECTION 1210 SURROUNDING MATERIALS
- SECTION 1211 [HCD 1 & HCD 2] GARAGE DOOR SPRINGS
- SECTION 1212 Reserved
- SECTION 1213 Reserved
- SECTION 1214 Reserved
- SECTION 1215 Reserved
- SECTION 1216 Reserved
- SECTION 1217 Reserved
- SECTION 1218 Reserved
- SECTION 1219 Reserved
- SECTION 1220 Reserved
- SECTION 1221 Reserved
- SECTION 1222 Reserved
- SECTION 1223 Reserved
- SECTION 1224 [OSHPD 1] HOSPITALS
- SECTION 1225 [OSHPD 2] SKILLED NURSING AND INTERMEDIATE-CARE FACILITIES
- SECTION 1226 [OSHPD 3] CLINICS
- SECTION 1227 [OSHPD 4] CORRECTIONAL TREATMENT CENTERS
- SECTION 1228 Reserved
- SECTION 1229 Reserved
- SECTION 1230 [CSA] MINIMUM STANDARDS FOR JUVENILE FACILITIES
- SECTION 1231 [CSA] LOCAL DETENTION
- SECTION 1232 Reserved
- SECTION 1233 Reserved
- SECTION 1234 Reserved
- SECTION 1235 [DPH] SANITARY CONTROL OF SHELLFISH (PLANTS AND OPERATIONS)
- SECTION 1236 [DPH] LABORATORY ANIMAL QUARTERS
- SECTION 1237 [DPH] WILD ANIMAL QUARANTINE FACILITIES
- SECTION 1238 Reserved
- SECTION 1239 Reserved
- SECTION 1240 [AGR] MEAT AND POULTRY PROCESSING PLANTS
- SECTION 1241 [AGR] COLLECTION CENTERS AND FACILITIES
- SECTION 1242 [AGR] RENDERERS
- SECTION 1243 [AGR] HORSEMEAT AND PET FOOD ESTABLISHMENTS
- SECTION 1244 Reserved
- SECTION 1245 Reserved
- SECTION 1246 Reserved
- SECTION 1247 Reserved
- SECTION 1248 Reserved
- SECTION 1249 Reserved
- SECTION 1250 [CA] PHARMACIES
- SECTION 1251 [CA] VETERINARY FACILITIES
- SECTION 1252 [CA] BARBER COLLEGES AND SHOPS
- SECTION 1253 [CA] SCHOOLS OF COSMETOLOGY, COSMETOLOGICAL ESTABLISHMENTS AND SATELLITE CLASSROOMS
- SECTION 1254 [CA] ACUPUNCTURE OFFICES
- Chapter 12 - Interior Environment
- [ 2010 California Building Code‚ Title 24‚ Part 2 (First Printing)‚ Includes Errata/Supplement through July 1‚ 2012 ]
SECTION 1203 VENTILATION
1203.1 General. Buildings shall be provided with natural ventilation in accordance with Section 1203.4, or mechanical ventilation in accordance with the California Mechanical Code.
Exception: [OSHPD 1, 2, 3 & 4] For restrictions on natural ventilation, see California Mechanical Code.
1203.2 Attic spaces. Enclosed attics and enclosed rafter spaces formed where ceilings are applied directly to the underside of roof framing members shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain and snow. Blocking and bridging shall be arranged so as not to interfere with the movement of air. A minimum of 1 inch (25 mm) of airspace shall be provided between the insulation and the roof sheathing. The net free ventilating area shall not be less than 1/300 of the area of the space ventilated, with 50 percent of the required ventilating area provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet (914 mm) above eave or cornice vents with the balance of the required ventilation provided by eave or cornice vents.
[BSC] Exception: Attic ventilation shall not be required when determined not necessary by the building official due to atmospheric or climatic conditions.
1203.3 Under-floor ventilation. The space between the bottom of the floor joists and the earth under any building except spaces occupied by basements or cellars shall be provided with ventilation openings through foundation walls or exterior walls. Such openings shall be placed so as to provide cross ventilation of the under-floor space.
1203.4 Natural ventilation. Natural ventilation of an occupied space shall be through windows, doors, louvers or other openings to the outdoors. The operating mechanism for such openings shall be provided with ready access so that the openings are readily controllable by the building occupants.
[HCD 1] In employee housing, all openable windows in rooms used for living, dining, cooking or sleeping purposes, and toilet and bath buildings, shall be provided and maintained with insect screening.
[HCD 1] Door openings of rooms used for dining, cooking, toilet and bathing facilities in employee housing shall be provided and maintained with insect screening or with solid doors equipped with self-closing devices in lieu thereof, when approved by the enforcement agency.
[HCD 1] The windows, doors, louvers or other approved closeable openings not required by Section 1029 may open into a passive solar energy collector for ventilation required by this section. The area of ventilation openings to the outside of the passive solar energy collector shall be increased to compensate for the openings required by the interior space.
Exception: Exterior openings required for ventilation shall be permitted to open into a thermally isolated sunroom addition or patio cover provided that the openable area between the sunroom addition or patio cover and the interior room shall have an area of not less than 8 percent of the floor area of the interior room or space, but not less than 20 square feet (1.86 m2). The minimum openable area to the outdoors shall be based on the total floor area being ventilated.1203.5 Other ventilation and exhaust systems. Ventilation and exhaust systems for occupancies and operations involving flammable or combustible hazards or other contaminant sources as covered in the California Mechanical Code or the California Fire Code shall be provided as required by both codes.
Exception: [OSHPD 1, 2, 3 & 4] For restrictions on natural ventilation, see California Mechanical Code.
[BSC] Exception: Attic ventilation shall not be required when determined not necessary by the building official due to atmospheric or climatic conditions.
1203.2.1 Openings into attic.
1203.3.1 Openings for under-floor ventilation.
1. Perforated sheet metal plates not less than 0.070 inch (1.8 mm) thick.
2. Expanded sheet metal plates not less than 0.047 inch (1.2 mm) thick.
3. Cast-iron grilles or gratings.
4. Extruded load-bearing vents.
5. Hardware cloth of 0.035 inch (0.89 mm) wire or heavier.
6. Corrosion-resistant wire mesh, with the least dimension not exceeding 1/8 inch (3.2 mm).
1203.3.1.1 [SPCB]
1203.3.2 Exceptions.
1. Where warranted by climatic conditions, ventilation openings to the outdoors are not required if ventilation openings to the interior are provided.
2. The total area of ventilation openings is permitted to be reduced to 1/1,500 of the under-floor area where the ground surface is covered with a Class I vapor retarder material and the required openings are placed so as to provide cross ventilation of the space. The installation of operable louvers shall not be prohibited.
3. Ventilation openings are not required where continuously operated mechanical ventilation is provided at a rate of 1.0 cubic foot per minute (cfm) for each 50 square feet (1.02 L/s for each 10 m2) of crawl space floor area and the ground surface is covered with a Class I vapor retarder.
4. Ventilation openings are not required when the ground surface is covered with a Class I vapor retarder, the perimeter walls are insulated and the space is conditioned in accordance with the California Energy Code.
5. For buildings in flood hazard areas as established in Section 1612.3, the openings for under-floor ventilation shall be deemed as meeting the flood opening requirements of ASCE 24 provided that the ventilation openings are designed and installed in accordance with ASCE 24.
6. [SPCB] For purposes of structural pest control inspections, ventilation shall be considered inadequate when the lack thereof has contributed to the growth of wood-destroying pests or organisms.
[HCD 1] In employee housing, all openable windows in rooms used for living, dining, cooking or sleeping purposes, and toilet and bath buildings, shall be provided and maintained with insect screening.
[HCD 1] Door openings of rooms used for dining, cooking, toilet and bathing facilities in employee housing shall be provided and maintained with insect screening or with solid doors equipped with self-closing devices in lieu thereof, when approved by the enforcement agency.
[HCD 1] The windows, doors, louvers or other approved closeable openings not required by Section 1029 may open into a passive solar energy collector for ventilation required by this section. The area of ventilation openings to the outside of the passive solar energy collector shall be increased to compensate for the openings required by the interior space.
1203.4.1 Ventilation area required.
1203.4.1.1 Adjoining spaces.
Exception: Exterior openings required for ventilation shall be permitted to open into a thermally isolated sunroom addition or patio cover provided that the openable area between the sunroom addition or patio cover and the interior room shall have an area of not less than 8 percent of the floor area of the interior room or space, but not less than 20 square feet (1.86 m2). The minimum openable area to the outdoors shall be based on the total floor area being ventilated.
1203.4.1.2 Openings below grade.
1203.4.2 Contaminants exhausted.
1203.4.2.1 Bathrooms.
1203.4.3 Openings on yards or courts.

